Product feature
Fan coil units are mainly composed of centrifugal fans and coil heat exchangers. It is the terminal device of the central air conditioning system. And the fan sends indoor air or outdoor mixed air through the air cooler to be cooled or heated and then sends the air into the room to lower or raise the indoor temperature to meet people's comfort requirements.
The advantage
1)Low noise.
2)Easy installation.
3)Special design of air filter.
4)Air flows: 340m3/h to 2380m3/h.
5)Cooling capacity range: 1.98kw to 12.9kw.
6)Power supply: 220V/50Hz, and depends on the client according to different country.
7)Used for:Industry,hotel,commercial bulding,etc.
8)Function:cooling only,cooling and heating.
9)Test condition for rated refrigerating output of fan coil unit.
10)Cooling working condition: Air inlet temperature of dry ball is 27ºC, temperature of wet ball is 19.5ºC. Water inlet temperature is 7ºC, temperature difference is 5ºC.
11)Heating working condition: Air inlet temperature of dry ball is 21ºC, water inlet temperature is 60ºC.
Model and Performance | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | ||
Rated air volume m3/h | High | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
Medium | 260 | 390 | 510 | 640 | 770 | 1020 | 1280 | 1530 | 1790 | ||
Low | 170 | 260 | 340 | 430 | 510 | 680 | 850 | 1020 | 1190 | ||
Rated cooling capacity KW | H | 1.98 | 2.8 | 3.87 | 4.58 | 5.42 | 7.38 | 9.08 | 11.1 | 12.9 | |
H | 1702 | 2408 | 3328 | 3938 | 4661 | 6346 | 7808 | 9546 | 11094 | ||
Rated heating capacity KW | H | 3.39 | 4.5 | 6.35 | 7.45 | 9.22 | 12.4 | 16.3 | 19.5 | 20.2 | |
H | 2915 | 3870 | 5460 | 6407 | 7930 | 10665 | 14020 | 16770 | 17370 | ||
Input power W | 12Pa | H | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 | 228 |
30Pa | H | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 | |
50Pa | H | 49 | 66 | 84 | 100 | 118 | 174 | 210 | 250 | 300 | |
Noise dB(A) | 12Pa | H | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
30Pa | H | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | |
50Pa | H | 42 | 44 | 46 | 47 | 49 | 50 | 52 | 54 | 56 | |
Water flow rate Kg/h | 350 | 510 | 660 | 800 | 980 | 1280 | 1600 | 1920 | 2230 | ||
Water resistance Kpa | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 40 | 50 | ||
Power supply | 220V/50Hz |
Our Company
Our Certification
FAQ
Q1:Could you assure your quality?
A1: All our products with CE certificate.,and units will be tested before package and the Qualified rate is up to 100%.
Q2:How long is your delivery date?
A2:3-5 days after receiving the payment.(Custom products excluded)
Q3:How long is the warranty?
A3:1 year warranty for free if confirmed by both side damage in the quality reason.
Q4:Are you a manufacture or trade company?
A4:We are a manufacture and welcome you to visit our factory.
Q5. What is your terms of packing?
A5: Generally, we pack our goods in neutral blank boxes and brown cartons.
If you have legally registered patent, we can pack the goods in your branded boxes after getting your authorization letters.
Our service
Pre-Sales Service
*Tell customers how to use our products and matters needing attention.
* Guide customers to choose the best and economic product, recover the investment within short time. .
* Site inspection if you need.
After-Sales Service
* If the project needs our installation guidance, we can send our engineer and translator. We can also send customers installation video to teach them how to fix and operate with our product.*Usually, our product warranty is 18 months after leaving factory or 12 months after installation. Within this months, all parts broken will be responsible for our factory.